Description
Honeywell Satronic burner control box DKG972-N Mod.5 แทนรุ่น TFI.2B-5
For 2-stage atmospheric gas burners
TECHNICAL DATA
Operating voltage 220 / 240 V (-15… +10%)
50 Hz (±5%)
or 110 / 120 V (-15… +10%)
60 Hz (±5%)
Fuse rating 10 A fast, 6 A slow
Power consumption ca. 12 VA
Max. load per output
– term. 3 ignition trafo 1.0 A, cos ϕ 0.2
– term. 5 + 6 solenoid valves 0.5 A, cos ϕ 0.4
– term. 7 alarm indicator 0.5 A, cos ϕ 0.4
– term. 4 auxiliary blower 2.0 A, cos ϕ 0.4
total load 4.0 A, cos ϕ 0.4
max. 16 A during 0,5 sec
Reset time from lock out none